Agents
You can check if ipmi/snmp simulators are up & running by issuing status command:
simengine-cli status --asset-key={key} --agent
UPS
SNMP Configurations
You can configure both IP & port of the snmpsim instance:
simengine-cli model create ups -k=3 --name=an-ups01 --host=192.168.124.3 --port=161
or
simengine-cli model update ups -k=3 --name=an-ups01 --host=localhost --port=1024
Note : binding to 161
requires root
access.
Charge & Drain Speed Factors
simengine
supports speed-up for both battery recharge and drain.
simengine-cli configure-state ups -k2 --charge-speed=50
simengine-cli configure-state ups -k2 --drain-speed=50
This factor will be multiplied by the estimated drain/charge percentage per second.
Note that running this command does not require simengine-core restart.
Runtime Graph
You can configure UPS runtime chart; For example, runtime.json
file will map 50 watts to 32 minutes, 100 to 18 min, 200 to 9 min etc.
runtime.json:
{
"50": 32,
"100": 18,
"200": 9,
"300": 5,
"400": 3,
"500": 2
}
Updating the model:
simengine-cli model update ups -k2 --runtime-graph "$(cat ./runtime.json)"
Power Capacity
Asset's power capacity can be updated as simengine-cli model update ups -k2 --power-capacity=1500
Full Recharge Time & Min Battery Level
Full recharge time can be configured as following:
simengine-cli model update ups -k2 --full-recharge-time=1 # set to 1 hour
The UPS will take 1 hour to recharge a fully depleted battery.
UPS also supports minimum battery level required (before UPS can power up its output outlets):
simengine-cli model update ups -k2 --min-power-bat=1 # 0.1% required before power is restored
Vendor Pre-Set
The simengine defaults its SNMP interface settings to APC hardware (outlined here ups). Custom vendor presets can be passed to the simengine-cli
system modelling tool with the --snmp-preset=/path/to/my_specs.json
option.
You can find APC examples of .json config files in simengine repo:
General Configurations (snmp-preset file description)
JSON property | Description |
---|---|
staticOidFile | .snmprec file containing recorded OID tree (see snmpsim doc reference). The simengine will search for the specified file at SIMENGINE_STATIC_DATA path |
assetName | Name displayed on the UI (can be overwritten with --name option) |
numOutlets | Number of UPS output outlets |
fullRechargeTime | (hours) Recharge time for a fully depleted battery |
minPowerOnBatteryLevel | Minimum value of the battery charge before UPS powers up its output |
outputPowerCapacity | (Watts) UPS output power capacity |
modelRuntime | Runtime graph consisting of key-value pairs { wattage: expected runtime in minutes } More values should yield more accurate results |
OID Specifications
OID JSON structure:
"OIDName": {
"OID": "1.3.6....", // Vendor-specific OID
"dataType": 2, // DataType (e.g. 2-iteger, 67-Timeticks, 66-Gauge etc.)
"defaultValue": 1, // Value set on engine start
"oidDesc": { // Value to enum mappings
"`1`": "switchOn",
"`2`": "switchOff"
}
}
JSON Property (OID Name) | Description | Value Mappings |
---|---|---|
SerialNumber | Asset serial number | |
HighPrecBatteryCapacity | High-precision battery capacity (max 1000) | |
AdvBatteryCapacity | Advance battery capacity (max 100%) | |
BasicBatteryStatus | Basic status of the UPS battery | batteryNormal, batteryLow |
HighPrecOutputLoad | High-precision load percentage of the total capacity (outputPowerCapacity) | |
AdvOutputLoad | load percentage of the total capacity (outputPowerCapacity) | |
HighPrecOutputCurrent | Current UPS load in AMPs (high-precision) | |
AdvOutputCurrent | Current UPS load in AMPs | |
BatteryRunTimeRemaining | Run-time left before UPS shuts down | |
TimeOnBattery | How long UPS has been running on a battery | |
PowerOff | Power off UPS device | switchOff,switchOffGraceful |
BasicOutputStatus | Battery status: online, on-battery, offline | onLine, onBattery, off |
InputLineFailCause | Reason behind transferring to the alt. battery power source | noTransfer, blackout, deepMomentarySag |
AdvConfigReturnDelay | Power up delay | |
AdvConfigShutoffDelay | Shut down delay |
Server Type
Server asset can manage VMs state and control its power. It supports up to 2 PSUs at the moment and requires power consumption and valid VM domain name specified (--domain-name={my_vm}
argument).
Server with IPMI_SIM interface (server-bmc
) requires specific .xml
configurations for qemu VM. You can edit libvirt
config file
by issuing this command:
virsh edit {domain name}
You will need to change the top-level tag to <domain type='kvm' xmlns:qemu='http://libvirt.org/schemas/domain/qemu/1.0'>
and also add qemu
command line arguments (after </devices>
) as following:
<qemu:commandline>
<qemu:arg value='-chardev'/>
<qemu:arg value='socket,id=ipmi0,host=localhost,port=9002,reconnect=10'/>
<qemu:arg value='-device'/>
<qemu:arg value='ipmi-bmc-extern,id=bmc0,chardev=ipmi0'/>
<qemu:arg value='-device'/>
<qemu:arg value='isa-ipmi-bt,bmc=bmc0'/>
<qemu:arg value='-serial'/>
<qemu:arg value='mon:tcp::9012,server,telnet,nowait'/>
</qemu:commandline>
Here's a sample model consisting of 2 outlets, 1 PDU, microwave and a server (controlling a VM named fedora27
):
# Create 2 outlets, one powers PDU another one powers PSU2
simengine-cli model create outlet --asset-key=1
simengine-cli model create outlet --asset-key=2
# Add a PDU
simengine-cli model create pdu --asset-key=3 --port=1024
# Add one useless microwave
simengine-cli model create static --asset-key=4 --name='Panasonic' --img-url=http://z3central.cdot.systems/docs/microwave-159076_640.png --power-source=120 --power-consumption=120
# Add server that supports BMC & IPMI
simengine-cli model create server-bmc -k=5 --domain-name=fedora27 --power-consumption=480 --psu-num=2 --psu-load 0.5 0.5
# Power up the components
simengine-cli model power-link --source-key=1 --dest-key=3
simengine-cli model power-link --source-key=31 --dest-key=4
simengine-cli model power-link --source-key=35 --dest-key=51
simengine-cli model power-link --source-key=2 --dest-key=52
The IPMI interface can be queried as:
ipmitool -H localhost -p 9001 -U ipmiusr -P test sdr list
ipmitool -H localhost -p 9001 -U ipmiusr -P test power status
SNMP interface can be queried as:
snmpget -c public -v 1 127.0.0.1:1024 1.3.6.1.4.1.318.1.1.12.3.3.1.1.4.3
snmpwalk -c public -v 1 127.0.0.1:1024